4.2.7.5 Remote control self-checking procedure
When to use the OK button:
1 When the remote control displays an operating fault.
2 For periodic maintenance checks.
Step
No.
Action required
1 Switch on the power source.
2
Press the following three buttons simultaneously.
(The buttons may be pressed when the system is running)
TEMP MODE
5
3
The LCD screen will change, as shown below.
No. LCD indication Indication period (seconds)
1
â
For 1 second
2
â
For 1 second
3
â
For 1 second
4
â
For 1 second
5
â
For 3 seconds
To delete EEPROM memory only, press the three following buttons simultaneously
during the LCD screen changes.
TEMP MODE
5
Go to 11
4 Once the LCD screen has changed, the RUN indicator will ash twice.
01
5
The LCD screen will change, as shown below.
Press all buttons (13), one at a time. Each time the button is pressed, the indication
number shown in part (A) of the following diagram will increase by one.
-
The check cannot proceed to the next step until all the buttons are pressed.
Part A
00
02
NOTE
The buttons may be pressed in any order.
If two or more switches are pressed at once, the action is not valid and is therefore not registered.