4 Individual remote controls
PC-ARH
TCGB0106 rev.0 - 12/2014
169
4
FC Cooling Lower Limit for Setting Temperature
This function is used to limit the lowest setting temperature for FAN/COOL/DRY operations.
When this function is valid, it provides the adequate cooling operation and energy-saving effect.
The setting conditions and the cooling lower limit for the setting temperature are as follows:
Example:
Setting Temperature at Remote Control Switch
Available to Set Temperature
Not Available to Set Tem-
perature
Factory-Setting: “00”
(Lower Limit 19+0=19 ºC)
Setting Condition: “06”
(Lower Limit 19+6=25 ºC)
Available to Set Temperature
Setting Condition Details Setting Temperature Lower Limit (FAN/COOL/DRY) *
00 Standard Value 19 ºC
01 Lower Limit +1 ºC 20 ºC
02 Lower Limit +2 ºC 21 ºC
Omitted 03 to 08
.
.
.
.
.
.
09 Lower Limit +9 ºC 28 ºC
10 Lower Limit +10 ºC 29 ºC
* In case of Standard Unit
Fd Heating Upper Limit for Setting Temperature
This function is used to limit the highest setting temperature for HEAT operation.
When this function is valid, it provides the adequate heating operation and energy-saving effect. The setting conditions and
the heating upper limit for the setting temperature are as follows:
Example:
Setting Temperature at Remote Control Switch
Available to Set Temperature
Not Available to
Set Temperature
Factory-Setting: “00”
(Lower Limit 30-0=30 ºC)
Setting Condition: “09”
(Lower Limit 30-9=21 ºC)
Available to Set Temperature
Setting Condition Details Setting Temperature Upper Limit (HEAT) *
00 Standard Value 30 ºC
01 Upper Limit -1 ºC 29 ºC
02 Upper Limit -2 ºC 28 ºC
Omitted 03 to 08
.
.
.
.
.
.
09 Upper Limit -9 ºC 21 ºC
10 Upper Limit -10 ºC 20 ºC