6 Building air conditioning controls
CSNET WEB (PSC-A160WEB1)
TCGB0106 rev.0 - 12/2014
448448
Notify settings congures who will receive the notications and what will be the interval of these notications.
- Notify interval: you can set a notication interval of 1, 2, 6, 12 hours or 1 day.
- Notify E-Mail address: sets the name and the e-mail address of the different receivers.
On OK button the conguration will be saved and sent to the CSNET WEB, this operation is not immediately. When CSNET
WEB will receive and process this information you could see this on the alarm conguration eld.
In case of alarm, CSNET WEB will send an e-mail with the following contents:
From CSNET WEB Interface: From Computer:
CSNET WEB Alarm detected
(x,y) Alarm: #
(x,y) Alarm: #
(x,y) Alarm: #
(x,y) Alarm: #
OU IU Location Alarm
X Y L #
X Y L #
In both cases, each parameter is:
X: Outdoor unit number
Y: Indoor unit number
#: Alarm code
L: Location (just from client)
Backup copy
This option lets you make a backup copy of the CSNET WEB parameters. The Backup button saves the conguration in
the le you choose of the computer from which you accessed the system.
The Restore button re-establishes the conguration stored in the le you have specied.
Conguration report
Conguration report prints on a text le all the settings that CSNET WEB has.
The purpose of that is in case of wrong behaviour of the functions, report the state and help to understand if there is some-
thing not well congured.