6 Building air conditioning controls
CSNET Manager LT/XT
TCGB0106 rev.0 - 12/2014
554554
The differences between the congurations are:
- CSNET Manager
a. Conguring the mail alarms on the CSNET Manager is used when CSNET Manager is on a LAN net that does not
pass through a proxy to connect to Internet.
b. The mail alarms are being sent from the CSNET Manager when CSNET Manager software is running, so that the
device cannot be switched-off.
c. That connection allows the use of already existing SMTP servers on the Internet, such as Gmail, Yahoo or others.
These are encrypted connections, so they can be used.
d. The e-mail sent has the location information column as it is managed from the computer and it is powerful than
CSNET WEB interface.
ROUTER
HITACHI installation
SMTP server
LAN
H-LINK
HC-A64 NET
CSNET Manager
INTERNET
- CSNET WEB Interface:
a. Conguring the mail alarms on the CSNET WEB Interface is used when CSNET WEB is on a LAN that uses proxy
to connect to Internet.
b. CSNET WEB device will send the alarm mails using this SMTP server.
c. It is required to have a SMTP server on the same LAN than CSNET WEB.
d. CSNET WEB Interface cannot connect to a SMTP encrypted server.
PROXY
HITACHI installation
SMTP server
LAN
H-LINK
PSC-A160WEB1
INTERNET
Account details
The account details need to specify the next elds:
- Name: installation name.
- E-mail: account installation mail.
- Delivery Server address: mail server address.
- Server Port: mail server port.
- User name: mail user name.
- Password: mail password.