6 Building air conditioning controls
CSNET Manager LT/XT
TCGB0106 rev.0 - 12/2014
569569
6
Power meter
Power Meter tab lets the user congure a TCP-MODBUS power meter for each outdoor unit.
For each power meter device there should be entered the following parameters:
IP Address: LAN address of the power meter.
Power Meter ID: identier to know which of the power meters is used.
Registers: The Modbus Address and the measurement unit of each of the four variables available on the table should
be congured by the user according to the specic power meter information.
CAUTION
Suggested device tested by Hitachi is 7KM PAC3200 by Siemens.
Ensure that your Modbus-TCP power meter register starts at 0. CSNET Manager considers it like this, so if it starts at 1, subtract 1 to
each register address.
If CSNET Manager device is off it will not get power data.