Optional functions list
Items Optional Function
Indi-
vidual
setting
Setting
condition
Contents
b1
Cancellation
of heating
temperature
compensation due
to uneven heat
load
â—‹
00
Standard +4 ºC
01
Removal (offset
elimination)
02
Set temperature +2
o
C
(*1)
b2
Circulator function
at heating Thermo-
OFF
â—‹
00
01
Not available
Available
b3
Enforced 3 Minutes
minimum operation
time of compressor
â—‹
00
01
Not available
Available
b4
Change of lter
cleaning time
â—‹
00
01
02
03
04
Standard
100 hrs
1,200 hrs
2,500 hrs
No indication
b5
Fixing of operation
mode
×
00
01
Standard
Fixed
b6
Fixing of setting
temperature
×
00
01
Standard
Fixed
b7
Fixing of operation
as exclusive
cooling unit
×
00
01
Standard
Fixed
b8
Automatic COOL/
HEAT operation
×
00
01
Not available
Available
b9
Fixing of fan speed ×
00
01
Standard
Fixed
bA
Not prepared × -
Not used
bb
Cooling
temperature
compensation due
to uneven heat
load
×
00
Standard (No
Compensation)
01
Set Temp. –1
o
C
02
Set Temp. 2
o
C
bC
Not prepared -
00
01
Not used
(Use as 00 conditions)
bd
Not prepared -
00
01
Not used
(Use as 00 conditions)
bE
Not prepared -
00
01
Not used
(Use as 00 conditions)
C1
Not prepared -
00
01
Not used
(Use as 00 conditions)
C2
Not prepared - -
Not used
C3
HA function (only
for Japanese
market)
â—‹
00
01
Not available
(Use as 00 conditions)
C4
Drain Pump
Operation at
Heating
â—‹
00
01
Not available
Available
Items Optional Function
Indi-
vidual
setting
Setting
condition
Contents
C5
Hi speed (Except
for Hi Speed at
Heating Thermo-
OFF)
â—‹
00
01
02
Not available
Hi Speed 1 (*2)
Hi Speed 2
C6
Hi speed at heating
Thermo-OFF
â—‹
00
01
Not available
Available
C7
Canceling of
enforced 3 minutes
minimum
operation time of
compressor
â—‹
00
01
Standard
Cancellation
C8
Thermistor of
remote control
switch
â—‹
00 Not available
01
Control by thermistor of
remote control switch
02
Control by average
value of indoor suction
thermistor and thermistor
of remote control switch
C9
Not prepared - - Not used
CA
Not prepared - - Not used
Cb
Selection of forced
stoppage logic
×
00
Forced stoppage input:
A Contact
01
Forced stoppage input:
B Contact
CC
Not prepared ×
00
01
Not used
(Use as 00 conditions)
Cd
Not prepared -
00
01
Not used
(Use as 00 conditions)
CE
Not prepared -
00
01
Not used
(Use as 00 conditions)
CF
Change of louver
swing angle
â—‹
00
Standard (7-Step
Operation)
01
Cold draft prevention
(5
Steps: lower 2 steps cut
off)
02
High ceiling (5 Steps:
upper 2 steps cut off)
d1
Power supply ON/
OFF 1
â—‹
00
01
Not available
Available
d2
Not prepared - - Not used
d3
Power supply ON/
OFF 2
â—‹
00
01
Not available
Available
d4
Prevention for
cooling discharge
air temperature
decrease
â—‹
00
01
Not available
Available
d5
Prevention for
heating discharge
air temperature
decrease
â—‹
00
01
Not available
Available
4 Individual remote controls
PC-ARF
TCGB0106 rev.0 - 12/2014
70

Table of Contents

Other manuals for Hitachi PSC-A1T

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hitachi PSC-A1T and is the answer not in the manual?

Hitachi PSC-A1T Specifications

General IconGeneral
BrandHitachi
ModelPSC-A1T
CategoryController
LanguageEnglish

Related product manuals