Specifications - HC900 Analog Input Ranges vs. UMC800 Analog Input ranges 
202   HC900 Process Controller Installation and User Guide  Revision 19 
    06/14 
Type  Range 
Low 
Range High  EU  (Reference): Corresponding 
UMC800 Input type and range 
MV  -50  50    mV  -50  50  93 
MV  -100  100    mV –100 100  96 
MV  -500  500    mV –500 500  98 
V  0  1     V   0   1  101 
V  0  2     V   0   2  103 
V  0  5     V   0   5  105 
V  0  10     V  0  10  108 
V  1  5     V   1   5  107 
V  -1  1     V   -1   1  102 
V  -2  2     V   -2   2  104 
V  -5  5     V   -5   5  106 
V  -10  10     V  -10  10  109 
Carbon  0  1250  mV  n/a 
Oxygen  -30  510  mV  n/a