Appendix - Installation of Remote Termination Panels (RTPs) - Analog Input/Digital Input/Digital Output/Analog 
Output 
Revision 19   HC900 Process Controller Installation and User Guide  225 
06/14 
16 Point AC Digital Input 
Step  Action 
4  Connect field wiring. 
Note: S-L1 in the wiring figure below refers to power that is disconnected from these screw terminals when 
switch SW1 is open (0). 
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
21 22 23 24 25 26 27 28 29
30 31
32
33 34 35 36
37 38 39 40
IN1
IN2
IN3
IN4
IN5
IN6
IN7
IN8
IN9
IN10
IN11
IN12
IN13
IN14
IN15
IN16
L2
IN1+
IN2+
IN9+
IN10+
IN5+
IN6+
L2
IN3+
IN4+
IN7+
IN8+
L2
L2
L2
IN11+
IN12+
IN13+
IN14+
IN15+
IN16+
S
-
L1
S
-
L1
L1
S
-
L1
S
-
L1
S
-
L1
S
-
L1
S
-
L1
S
-
L1
S
-
L1
S
-
L1
S
-
L1
S
-
L1
S
-
L1
S
-
L1
S
-
L1
S
-
L1
S
-
L1
S
-
L1
S
-
L1
L1
Install jumper wires
 
 
 
16 Point DC Digital Output 
Step  Action 
1  ATTENTION: RTP and cables are intended for permanent installation within their own enclosure. 
ATTENTION: 16 point DC Digital Output is rated at 8A per module and 1A per output. Limited to 4A 
per group of 8. 
ATTENTION: The RTP combines the two groups of 8 outputs into one group of 16. 
Mount RTP cable assembly to HC900 Controller (Figure 92). 
•  Remove appropriate key tabs from terminal board to allow mating with the module. See page 75. 
•  Connect desired cable to 16 point DC DO module at controller. Choose from: 
900RTC-L010  Remote Terminal Low Voltage Cable Assembly, 1.0 meters long 
900RTC-L025  Remote Terminal Low Voltage Cable Assembly, 2.5 meters long 
900RTC-L050  Remote Terminal Low Voltage Cable Assembly, 5.0 meters long 
•  Install 16 point DC DO label into the module connector cover. 
•  Connect shield drain wire to the grounding bars at the base of the HC900 rack. All field-wiring 
shields must be grounded as described in the shield grounding section (page 70).