Appendix - Installation of Remote Termination Panels (RTPs) - Analog Input/Digital Input/Digital Output/Analog
Output
234 HC900 Process Controller Installation and User Guide Revision 19
06/14
16 Point Analog Output
Step Action
1 ATTENTION: RTP and cables are intended for permanent installation within their own enclosure.
Mount RTP cable assembly to HC900 Controller (Figure 92).
Remove appropriate key tabs from terminal board to allow mating with the module. See page 75.
Connect terminal block end of desired cable assembly to 16 point Analog Output module at
controller. Choose from:
900RTC-3210 Remote Terminal Cable assembly, 1.0 meters long
900RTC-3225 Remote Terminal Cable assembly, 2.5 meters long
900RTC-3250 Remote Terminal Cable assembly, 5.0 meters long
Install 16 point Analog Output label into the module connector cover.
Connect both shield drain wires to the grounding bars at the base of the HC900 rack. All field-wiring
shields must be grounded as described in the shield grounding section (page 70).
2 Mount RTPs to DIN rail.
Latch to rail. See page 244.
Connect cables to RTPs. Cables are markedRTP A” and “RTP B. In step 4, RTP A will be wired to
Inputs 1-10, RTP B to Inputs 9-16. You can write on the RTPs’ labels to distinguish them.
Note: Inputs 9 and 10 are wired between both RTPs.
3 Set/verify jumper positions on each RTP as shown.
Jumper open
Jumper closed
Module Removal / Insertion Under Power (RIUP) is supported by turning off Switch SW1 to allow removal of
the module from the rack without causing an arc. See page 73.
ATTENTION: SW1 opens the + side of the External 24V Power so that RIUP of module is possible.
See page 233 for RTP internal schematic.