WindO/I-NV4 Users Manual 30-27
3 Analog I/O Modules
30
Expansion Modules
Mixed Analog I/O Module
Allocation of device address for the mixed analog I/O module is shown below.
For details about the parameter setting values for analog inputs, refer to “ Analog Input Parameter Setting Values” on
page 30-24. For analog outputs, refer to “ Analog Output Parameter Setting Values” on page 30-26.
Channel
Parameter R/W
FC6A-L06A1 FC6A-L03CN1
No. I/O Address Number I/O Address Number
CH0
Analog data R
Input
+0
Input
+0
Analog status R +1 +1
CH1
Analog data R +2 +2
Analog status R +3 +3
CH2
Analog data R +4
Output
+4
Analog status R +5 +5
CH3
Analog data R +6 ――
Analog status R +7 ――
CH4
Analog data R
Output
+8 ――
Analog status R +9 ――
CH5
Analog data R +10 ――
Analog status R +11 ――