EasyManua.ls Logo

IDEC MICRO/I HG1P-ST32 Series - Page 1478

IDEC MICRO/I HG1P-ST32 Series
1665 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3 Analog I/O Modules
30-26 WindO/I-NV4 User’s Manual
Analog Output Module
Allocation of device address for the analog output module is shown below.
For details about the parameter setting values, refer to “ Analog Output Parameter Setting Values” on page 30-26.
Analog Output Parameter Setting Values
The parameter setting values are as follows.
Signal type
If the setting value is outside the range, a parameter setting error will occur.
Data type
If the setting value is 2 to 65,535, a parameter setting error will occur.
Minimum and maximum values
The minimum and maximum values can be set only when the data type is set to optional range. Set the minimum and
maximum values between -32,768 and 32,767.
Channel
Parameter R/W
FC6A-K2A1 FC6A-K4A1
No. Address Number Address Number
CH0
Analog output data R +0 +0
Analog output status R +1 +1
CH1
Analog output data R +2 +2
Analog output status R +3 +3
CH2
Analog output data R +4
Analog output status R +5
CH3
Analog output data R +6
Analog output status R +7
Setting Value Signal Type
0 Unused
1 0 to 10 V
2 -10 to +10 V
3 0 to 20 mA
4 4 to 20 mA
Setting Value Data type
0 Binary data
1Optional range

Table of Contents