3 HG2G-5T, HG1G
35-50 WindO/I-NV4 User’s Manual
3.7
Installation
● Operating Environment
For designed performance and safety of the HG2G-5T, HG1G, do not install the HG2G-5T, HG1G in the following
environments:
• Where dust, briny air, or iron particles exist.
• Where oil or chemical splashes for long time.
• Where oil mist is filled.
• Where direct sunlight falls on the HG2G-5T, HG1G.
• Where strong ultraviolet rays fall on the HG2G-5T, HG1G.
• Where corrosive or combustible gasses exist.
• Where the HG2G-5T, HG1G is subjected to shocks or vibrations.
• Where condensation occurs due to rapid temperature change.
• Where high-voltage or arc-generating equipment (electromagnetic contactors or circuit protectors) exists in the vicinity.
●
Ambient Temperature
• Allow sufficient space for ventilation, and install the equipment away from heat sources.
• Allow at least 100mm between the HG2G-5T, HG1G and walls or other equipment.
• Do not install the HG2G-5T, HG1G where the ambient temperature exceeds the rated operating ambient
temperature range. When mounting the HG2G-5T, HG1G in such locations, provide a forced air-cooling fan or air-
conditioner to keep the ambient temperature within the rated temperature range.
●
HG2G-5T, HG1G Installation
• Make a panel cut-out on the panel with the dimensions shown below.
• Use the attached mounting clips to tighten the screws evenly to mount panel: screws must be applied on total of
four places on top and bottom with the specified torque.
Mounting clips can be attached to the left and right sides of HG4G and HG2G-5F. However, if they are attached in
such way, there is a risk of not satisfying product specifications such as waterproof performance, shock resistance,
and vibration resistance performance.
CAUTION
• Do not tighten with excessive force, otherwise the HG2G-5T, HG1G may warp and cause wrinkle
on the display, or impair the waterproof characteristics.
• If the mounting clips are tightened obliquely to the panel, the HG2G-5T, HG1G may fall off the panel.
• When installing the HG2G-5T, HG1G into a panel cut-out, make sure that the gasket is not twisted.
Especially when re-installing, take special care because any twists in the gasket will impair the
waterproof characteristics.
Unit: mm
Type No. A B Panel Thickness
HG2G-5T 121.0
+2.0
0
153.0
+2.0
0
1.0 to 5.0
HG1G 92.0
+1.0
0
118.0
+1.0
0
Mounting Clip
Mounting Clip
Panel
Unit: mm
Type No. Specified Torque
HG2G-5T 0.2 to 0.3
HG1G 0.3 to 0.35