Para.
No.
Address
Name
Value Range
Default
Unit
Change
Page
F9-51 63795
Fault protection action
selection 4
Ones: Accumulative running time
reach
(E26)
0: Coast to stop
1: Decelerate to stop
4: Warning
5: Disabled
Tens: User-defined fault 1 (E27)
0: Coast to stop
1: Decelerate to stop
4: Warning
5: Disabled
Hundreds: User-defined fault 2 (E28)
0: Coast to stop
1: Decelerate to stop
4: Warning
5: Disabled
Thousands: Accumulative power-on
time reach
(E29)
0: Coast to stop
1: Decelerate to stop
4: Warning
5: Disabled
Ten thousands: Load loss (E30)
0: Coast to stop
1: Decelerate to stop
4: Warning
5: Disabled
51111 -
At stop
F9-51
on page
306
List of Drive Unit Parameters