Para.
No.
Address
Name
Value Range
Default
Unit
Change
Page
A1-10 41226
AI active mode (used as
DI)
Ones:
0: Active high
1: Active low
Tens:
0: Active high
1: Active low
Hundreds:
0: Active high
1: Active low
0 -
At stop
“
A1-10
”
on page
354
A5-00 42240
DPWM switchover
frequency upper limit
0.00 Hz to 50.00 Hz 12.00 Hz At once
“
A5-00
”
on page
354
A5-01 42241 PWM modulation mode
0: Asynchronous modulation
1: Synchronous modulation
0 - At once
“
A5-01
”
on page
354
A5-02 42242
Dead-zone
compensation
0: Disabled
1: Enabled
1 -
At stop
“
A5-02
”
on page
355
A5-03 42243
Random PWM depth
0 to 10 0 - At once
“
A5-03
”
on page
355
A5-04 42244
Fast current limiting
0: Disabled
1: Enabled
0 - At once
“
A5-04
”
on page
355
A5-05 42245
Sampling delay
1 to 13 5 - At once
“
A5-05
”
on page
355
A5-06 42246
Undervoltage threshold
150.0 V to 455.0 V
Three-phase
400 V: 350.0 V
Single-phase
200 V: 200.0 V
V At once
“
A5-06
”
on page
356
A5-07 42247
SVC optimization mode
0: No optimization
1: Optimization mode 1
2: Optimization mode 2
1 -
At stop
“
A5-07
”
on page
356
A6-00 42496
Curve 4 minimum input
–10.00 V to 10.00 V 0.00 V At once
“
A6-00
”
on page
356
A6-01 42497
Percentage
corresponding to curve 4
minimum input
–100.0% to 100.0% 0.0 % At once
“
A6-01
”
on page
356
A6-02 42498
Curve 4 inflection point 1
input
–10.00 V to 10.00 V 3.00 V At once
“
A6-02
”
on page
357
A6-03 42499
Percentage
corresponding to curve 4
inflection point 1 input
–100.0% to 100.0% 30.0 % At once
“
A6-03
”
on page
357
List of Drive Unit Parameters