Para.
No.
Address
Name
Value Range
Default
Unit
Change
Page
A6-04 42500
Curve 4 inflection point 2
input
–10.00 V to 10.00 V 6.00 V At once
A6-04
on page
357
A6-05 42501
Percentage
corresponding to curve 4
inflection point 2 input
–100.0% to 100.0% 60.0 % At once
A6-05
on page
357
A6-06 42502
Curve 4 maximum input
–10.00 V to 10.00 V 10.00 V At once
A6-06
on page
357
A6-07 42503
Percentage
corresponding to curve 4
maximum input
–100.0% to 100.0% 100.0 % At once
A6-07
on page
358
A6-08 42504
Curve 5 minimum input
–10.00 V to 10.00 V –10.00 V At once
A6-08
on page
358
A6-09 42505
Percentage
corresponding to curve 5
minimum input
–100.0% to 100.0% –100.0 % At once
A6-09
on page
358
A6-10 42506
Curve 5 inflection point 1
input
–10.00 V to 10.00 V -3.00 V At once
A6-10
on page
358
A6-11 42507
Percentage
corresponding to curve 5
inflection point 1 input
–100.0% to 100.0% –30.0 % At once
A6-11
on page
358
A6-12 42508
Curve 5 inflection point 2
input
–10.00 V to 10.00 V 3.00 V At once
A6-12
on page
359
A6-13 42509
Percentage
corresponding to curve 5
inflection point 2 input
–100.0% to 100.0% 30.0 % At once
A6-13
on page
359
A6-14 42510
Curve 5 maximum input
–10.00 V to 10.00 V 10.00 V At once
A6-14
on page
359
A6-15 42511
Percentage
corresponding to curve 5
maximum input
–100.0% to 100.0% 100.0 % At once
A6-15
on page
359
A6-16 42512
AI1 gain
–10.00 to 10.00 1.00 - At once
A6-16
on page
360
A6-17 42513
AI1 offset
–100.0% to 100.0% 0.0 % At once
A6-17
on page
360
A6-18 42514
AI2 gain
–10.00 to 10.00 1.00 - At once
A6-18
on page
360
List of Drive Unit Parameters