Parameter Group
-281-
Description
The AC drive provides four groups of deceleration time, which can be switched by using the DI
terminal. This parameter defines the fourth group of deceleration time.
F8-09
Jump frequency 1
Address:
63497
Min.:
0.00
Unit:
Hz
Max.: 655.35 Data type: UInt16
Default:
0.00
Change:
At once
Value Range:
0.00 Hz to 655.35 Hz
Description
The jump frequency enables the AC drive to avoid any frequency at which a mechanical resonance
may occur. This parameter defines the first jump frequency. If it is set to 0, the first jump frequency is
canceled.
F8-10
Jump frequency 2
Address:
63498
Min.:
0.00
Unit:
Hz
Max.:
655.35
Data type: UInt16
Default:
0.00
Change:
At once
Value Range:
0.00 Hz to 655.35 Hz
Description
The jump frequency enables the AC drive to avoid any frequency at which a mechanical resonance
may occur. This parameter defines the second jump frequency. If it is set to 0, the second jump
frequency is canceled.
F8-11
Jump frequency amplitude
Address:
63499
Min.:
0.00
Unit:
Hz
Max.: 5.00 Data type: UInt16
Default:
0.00
Change:
At once
Value Range:
0.00 Hz to 5.00 Hz
Description
During acceleration, when the running frequency increases to a value that is close to the jump
frequency, the AC drive runs for a period at the current frequency and then skips over the jump
frequency. The jump range is twice the value of F8-11 (jump frequency amplitude).
During deceleration, when the running frequency decreases to a value that is close to the jump
frequency, the AC drive runs for a period at the current frequency and then skips over the jump
frequency. The jump range is twice the value of F8-11 (jump frequency amplitude).
F8-12
Jump frequency selection during acceleration/deceleration
Address:
63500
Min.:
0
Unit:
-
Max.: 1 Data type: UInt16
Default:
0
Change:
At once
Value Range:
0: Disabled
1: Enabled