Parameter Group
-282-
Description
This parameter defines whether to enable the jump frequency function during acceleration and
deceleration.
0: Disabled
The jump frequency function is disabled during acceleration and deceleration.
1: Enabled
The jump frequency function is enabled during acceleration and deceleration.
F8-13
FWD/REV Switchover Dead-zone Time
Address:
63501
Min.:
0.0
Unit:
s
Max.: 3000.0 Data type: UInt16
Default:
0.0
Change:
At once
Value Range:
0.0s to 3000.0s
Description
This parameter defines the transition time at 0 Hz output during transition between forward running
and reverse running.
F8-14
Reverse run enable
Address:
63502
Min.:
0
Unit:
-
Max.: 1 Data type: UInt16
Default:
0
Change:
At once
Value Range:
0: Reverse running allowed
1: Reverse running inhibited
Description
When F8-14 is active, the motor runs at zero frequency when a reverse run command is input to the
AC drive.
F8-15
Running mode when frequency reference below lower limit
Address:
63503
Min.:
0
Unit:
-
Max.: 2 Data type: UInt16
Default:
0
Change:
At once
Value Range:
0: Run at frequency lower limit
1: Stop
2: Run at zero speed
Description
0: Run at frequency lower limit
If the running frequency is lower than the frequency lower limit, the AC drive runs at the frequency
lower limit.
1: Stop
If the running frequency is lower than the frequency lower limit, the AC drive stops.
2: Run at zero speed
If the running frequency is lower than the frequency lower limit, the AC drive runs at zero speed.
F8-17
Normally open (NO) input of external fault
Address:
63505