Parameter Group
-283-
Min.:
0
Unit:
-
Max.: 1 Data type: UInt16
Default:
0
Change:
At stop
Value Range:
0: Always active
1: Active only in running
Description
This parameter defines DI function 10: external fault NO input mode.
0: Always active
E15.01 is reported whenever DI function 10 (external fault NO input) is triggered.
1: Active only in running
E15.01 is reported when DI function 10 (external fault NO input) is triggered during running.
F8-18
Normally closed (NC) input of external fault
Address:
63506
Min.:
0
Unit:
-
Max.: 1 Data type: UInt16
Default:
0
Change:
At stop
Value Range:
0: Always active
1: Active only in running
Description
This parameter defines DI function 11: external fault NC input mode.
0: Always active
E15.02 is reported whenever DI function 11 (external fault NC input) is triggered.
1: Active only in running
E15.02 is reported when DI function 11 (external fault NC input) is triggered during running.
F8-19
Accumulative power-on time threshold setting
Address:
63507
Min.:
0
Unit:
h
Max.: 65000 Data type: UInt16
Default:
0
Change:
At once
Value Range:
0 h to 65000 h
Description
This parameter defines the accumulative power-on time threshold of the AC drive. When F7-12
(accumulative power-on time) exceeds F8-19 (accumulative power-on time threshold), the DO/RO
terminal outputs an active signal.
F8-20
Accumulative running time threshold setting
Address:
63508
Min.:
0
Unit:
h
Max.: 65000 Data type: UInt16
Default:
0
Change:
At once
Value Range:
0 h to 65000 h
Description
This parameter defines the accumulative running time threshold of the AC drive. When F7-09
(accumulative running time) exceeds F8-20 (accumulative running time threshold), the DO/RO
terminal outputs an active signal.