Parameter Group
-284-
F8-21
Startup protection selection
Address:
63509
Min.:
0
Unit:
-
Max.: 1 Data type: UInt16
Default:
0
Change:
At once
Value Range:
0: Disabled
1: Enabled
Description
The AC drive is equipped with the startup protection function to prevent the motor from responding
to commands upon unexpected power-on or fault reset.
F8-22
Frequency detection value 1 (FDT1)
Address:
63510
Min.:
0.00
Unit:
Hz
Max.: 655.35 Data type: UInt16
Default:
50.00
Change:
At once
Value Range:
0.00 Hz to 655.35 Hz
Description
When the running frequency is higher than the frequency detection value (FDT1), the DO/RO terminal
outputs an active signal; when the running frequency is lower than the result of the frequency
detection value (FDT1) minus the frequency check hysteresis (FDT1), the DO/RO terminal outputs an
inactive signal. The valid value range is 0.00 Hz to F0-10 (maximum frequency).
F8-23
Frequency detection hysteresis 1 (FDT1)
Address:
63511
Min.:
0.00
Unit:
Hz
Max.:
655.35
Data type:
UInt16
Default:
2.50
Change:
At once
Value Range:
0.00 to F8-22
Description
When the running frequency is higher than F8-22, the DO/RO terminal outputs an active signal. When
the running frequency is lower than a specific value (F8-22 minus F8-23), the DO/RO terminal outputs
an inactive signal.
F8-24
Frequency detection value 2 (FDT2)
Address:
63512
Min.:
0.00
Unit:
Hz
Max.: 655.35 Data type: UInt16
Default:
50.00
Change:
At once
Value Range:
0.00 Hz to 655.35 Hz
Description
When the running frequency is higher than the frequency detection value (FDT2), the DO/RO terminal
outputs an active signal; when the running frequency is lower than the result of the frequency
detection value (FDT2) minus the frequency check hysteresis (FDT2), the DO/RO terminal outputs an
inactive signal. The valid value range is 0.00 Hz to F0-10 (maximum frequency).