Parameter Group
-285-
F8-25
Frequency detection hysteresis 2 (FDT2)
Address:
63513
Min.:
0.00
Unit:
Hz
Max.: 655.35 Data type: UInt16
Default:
2.50
Change:
At once
Value Range:
0.00 Hz to 655.35 Hz
Description
When the running frequency is higher than F8-24, the DO/RO terminal outputs an active signal. When
the running frequency is lower than a specific value (F8-24 minus F8-25), the DO/RO terminal outputs
an inactive signal.
F8-26
Frequency detection range
Address:
63514
Min.:
0.00
Unit:
Hz
Max.: 655.35 Data type: UInt16
Default:
2.50
Change:
At once
Value Range:
0.00 Hz to 655.35 Hz
Description
The DO terminal outputs an active signal when the running frequency of the AC drive is within the
specified range (frequency reference±F8-26).
F8-27
Detection value 1 for frequency reach
Address:
63515
Min.:
0.00
Unit:
Hz
Max.:
655.35
Data type:
UInt16
Default:
50.00
Change:
At once
Value Range:
0.00 Hz to 655.35 Hz
Description
When the running frequency of the AC drive is within the frequency detection range, the DO/RO
terminal outputs an active signal. The valid value range is 0.00 Hz to F0-10 (maximum frequency).
F8-28
Detection frequency 1 for frequency reach
Address:
63516
Min.:
0.00
Unit:
Hz
Max.: 655.35 Data type: UInt16
Default:
2.50
Change:
At once
Value Range:
0.00 to F8-27
Description
Frequency detection range = (Detection value 1 for frequency reach)±(Detection frequency 1 for
frequency reach). That is, the frequency detection rang is calculated using (F8-27)±(F8-28).
F8-29
Detection mode for frequency reach 1
Address:
63517
Min.:
0
Unit:
-
Max.: 1 Data type: UInt16
Default:
0
Change:
At stop
Value Range: