Parameter Group
-286-
0: Always detect
1: Not detect during acceleration/deceleration
Description
This parameter defines the frequency 1 reach detection mode.
When it is set to 0, the DO/RO terminal outputs an active signal if the detection condition is met.
When it is set to 1, the DO/RO terminal does not output an active signal during acceleration and
deceleration even if the detection condition is met.
F8-30
Detection value 2 for frequency reach
Address:
63518
Min.:
0.00
Unit:
Hz
Max.: 655.35 Data type: UInt16
Default:
50.00
Change:
At once
Value Range:
0.00 Hz to 655.35 Hz
Description
When the running frequency of the AC drive is within the frequency detection range, the DO/RO
terminal outputs an active signal. The valid value range is 0.00 Hz to F0-10 (maximum frequency).
F8-31
Detection frequency 2 for frequency reach
Address:
63519
Min.:
0.00
Unit:
Hz
Max.: 655.35 Data type: UInt16
Default:
2.50
Change:
At once
Value Range:
0.00 to F8-28
Description
Frequency detection range = (Detection value 2 for frequency reach)±(Detection frequency 2 for
frequency reach). That is, the frequency detection rang is calculated using (F8-30)±(F8-31).
F8-32
Detection mode for frequency reach 2
Address:
63520
Min.:
0
Unit:
-
Max.: 1 Data type: UInt16
Default:
0
Change:
At stop
Value Range:
0: Always detect
1: Not detect during acceleration/deceleration
Description
This parameter defines the frequency 1 reach detection mode.
When it is set to 0, the DO/RO terminal outputs an active signal if the detection condition is met.
When it is set to 1, the DO/RO terminal does not output an active signal during acceleration and
deceleration even if the detection condition is met.
F8-35
Switchover frequency of acceleration time 1 and acceleration time 2
Address:
63523
Min.:
0.00
Unit:
Hz
Max.: 655.35 Data type: UInt16
Default:
0.00
Change:
At once
Value Range:
0.00 Hz to 655.35 Hz