Parameter Group
-287-
Description
This function is used to switch the acceleration/deceleration time based on the running frequency
range when the AC drive is running. This function is available only when motor 1 is selected (F0-24 =
0) and the DI terminal is not assigned with function 18 (acceleration/deceleration time selection
terminal 1) or 19 (acceleration/deceleration time selection terminal 2).
The valid value range is 0.00 Hz to F0-10 (maximum frequency).
F8-36
Switchover frequency of deceleration time 1 and deceleration time 2
Address:
63524
Min.:
0.00
Unit:
Hz
Max.:
655.35
Data type: UInt16
Default:
0.00
Change:
At once
Value Range:
0.00 Hz to 655.35 Hz
Description
This function is used to switch the acceleration/deceleration time based on the running frequency
range when the AC drive is running. This function is available only when motor 1 is selected (F0-24 =
0) and the DI terminal is not assigned with function 18 (acceleration/deceleration time selection
terminal 1) or 19 (acceleration/deceleration time selection terminal 2).
The valid value range is 0.00 Hz to F0-10 (maximum frequency).
F8-37
Jog preferred
Address:
63525
Min.:
0
Unit:
-
Max.: 1 Data type: UInt16
Default:
0
Change:
At stop
Value Range:
0: Disabled
1: Enabled
Description
This parameter defines whether to set the highest priority to the terminal jog function. If it is set to 1,
the AC drive enters the jog running status immediately when any of F4-00 to F4-09 is set to 4 (forward
jog) or 5 (reverse jog).
F8-38
Zero current detection level
Address:
63526
Min.:
0.0
Unit:
%
Max.: 300.0 Data type: UInt16
Default:
5.0
Change:
At once
Value Range:
0.0% to 300.0%
Description
When the output current of the AC drive is lower than or equal to F8-38 (zero current detection level)
for longer than F8-39 (zero current detection delay), the DO/RO terminal outputs an active signal.
F8-39
Zero current detection delay
Address:
63527
Min.:
01
Unit:
s
Max.: 600.00 Data type: UInt16
Default:
0.10
Change:
At once
Value Range: