Parameter Group
-288-
0.01s to 600.00s
Description
When the output current of the AC drive is lower than or equal to F8-38 (zero current detection level)
for longer than F8-39 (zero current detection delay), the DO/RO terminal outputs an active signal.
F8-40
Output overcurrent threshold
Address:
63528
Min.:
0.0
Unit:
%
Max.: 300.0 Data type: UInt16
Default:
200.0
Change:
At once
Value Range:
0.0% to 300.0%
Description
When the output current of the AC drive is higher than F8-40 (output current threshold) for longer
than F8-41 (output overcurrent detection delay), the DO/RO terminal outputs an active signal.
F8-41
Software overcurrent detection delay
Address:
63529
Min.:
0.00
Unit:
s
Max.: 600.00 Data type: UInt16
Default:
0.00
Change:
At once
Value Range:
0.00s to 600.00s
Description
When the output current of the AC drive is higher than F8-40 (output current threshold) for longer
than F8-41 (output overcurrent detection delay), the DO/RO terminal outputs an active signal.
F8-42
Detection level of current 1
Address:
63530
Min.:
0.0
Unit:
%
Max.: 300.0 Data type: UInt16
Default:
100.0
Change:
At once
Value Range:
0.0% to 300.0%
Description
When the output current of the AC drive is within the range of F8-42 (current 1)±F8-43 (detection
width of current 1) x F1-03 (rated motor current), the DO/RO terminal outputs an active signal.
F8-43
Detection width of current 1
Address:
63531
Min.:
0.0
Unit:
%
Max.: 300.0 Data type: UInt16
Default:
0.0
Change:
At once
Value Range:
0.0% to 300.0%
Description
When the output current of the AC drive is within the range of F8-42 (current 1)±F8-43 (detection
width of current 1) x F1-03 (rated motor current), the DO/RO terminal outputs an active signal.
F8-44
Detection level of current 2
Address:
63532