Parameter Group
-289-
Min.:
0.0
Unit:
%
Max.:
300.0
Data type: UInt16
Default:
100.0
Change:
At once
Value Range:
0.0% to 300.0%
Description
When the output current of the AC drive is within the range of F8-44 (current 2)±F8-45 (detection
width of current 2) x F1-03 (rated motor current), the DO/RO terminal outputs an active signal.
F8-45
Detection width of current 2
Address:
63533
Min.:
0.0
Unit:
%
Max.: 300.0 Data type: UInt16
Default:
0.0
Change:
At once
Value Range:
0.0% to 300.0%
Description
Detection width of current 2 = F8-45 (detection width of current 2) x F1-03 (rated motor current)
F8-46
Timing function
Address:
63534
Min.:
0
Unit:
-
Max.: 1 Data type:
UInt16
Default:
0
Change:
At stop
Value Range:
0: Disabled
1: Enabled
Description
If F8-46 (timing function) is set to 1, the DO/RO terminal outputs an active signal when the current
operation time of the AC drive reaches the specified timing duration. The timing duration is set by F8-
47 and F8-48.
F8-47
Timing duration source
Address:
63535
Min.:
0
Unit:
-
Max.: 3 Data type: UInt16
Default:
0
Change:
At stop
Value Range:
0: F8-48
1: AI1
2: AI2
Description
When it is set to 0, the timing duration is set by F8-48.
When it is set to 1, the timing duration = (AI1 voltage/10 V) x F8-48. 100% of analog input corresponds
to the value of F8-48.
When it is set to 2, the timing duration = (AI2 voltage/10 V) x F8-48. 100% of analog input corresponds
to the value of F8-48.
F8-48
Timing duration
Address:
63536
Min.:
0.0
Unit: min
Max.: 6500.0 Data type: UInt16