Loading...
Parameter Group
-291-
When this parameter is set to 0, the fan works when the AC drive is running. When the AC drive stops,
the fan works if the heatsink temperature is higher than 40°C and stops if the heatsink temperature is
lower than 40°C.
When this parameter is set to 1, the fan keeps working after power-on.
Axis 2 of dual-axis drive unit:
F8-52 is not editable. The default value is 0, that is, the fan works when axis 2 of the dual-axis drive
unit is running.
F8-54
Wakeup frequency
Address:
63542
Min.:
0.00
Unit:
Hz
Max.: 655.35 Data type: UInt16
Default:
0.00
Change:
At once
Value Range:
Hibernation frequency (F8-56) to maximum frequency (F0-10)
Description
In hibernation state, when the frequency reference is equal to or higher than F8-54 (wakeup
frequency) and the current running command is valid, the AC drive starts directly after the delay set
by F8-50 (wakeup delay) elapses.
F8-55
Wakeup delay
Address:
63543
Min.:
0.0
Unit:
s
Max.: 6500.0 Data type: UInt16
Default:
0.0
Change:
At once
Value Range:
0.0s to 6500.0s
Description
In hibernation state, when the frequency reference is equal to or higher than F8-54 (wakeup
frequency) and the current running command is valid, the AC drive starts directly after the delay set
by F8-55 (wakeup delay) elapses.
F8-56
Hibernation frequency
Address:
63544
Min.:
0.00
Unit:
Hz
Max.: 655.35 Data type: UInt16
Default:
0.00
Change:
At once
Value Range:
0.00 Hz to wakeup frequency (F8-54)
Description
When the frequency reference is lower than or equal to F8-56 (hibernation frequency) during running,
the AC drive enters the hibernation state and coasts to stop after the time defined by F8-57
(hibernation delay) elapses.
F8-57
Hibernation delay
Address:
63545
Min.:
0.0
Unit:
s
Max.: 6500.0 Data type: UInt16
Default:
0.0
Change:
At once
Value Range:
0.0s to 6500.0s

Table of Contents