Parameter Group
-292-
Description
When the frequency reference is lower than or equal to F8-56 (hibernation frequency) during running,
the AC drive enters the hibernation state and coasts to stop after the time defined by F8-57
(hibernation delay) elapses.
F8-58
Current running time threshold
Address:
63546
Min.:
0.0
Unit: min
Max.: 6500.0 Data type: UInt16
Default:
0.0
Change:
At once
Value Range:
0.0 min to 6500.0 min
Description
When the current operation time reaches the value of F8-58, the DO/RO terminal outputs an active
signal. It is valid only for the current AC drive running. The previous operation time is not included.
F8-59
Switchover between communication addresses 2000H and 2001H
Address:
63547
Min.:
0
Unit:
-
Max.: 1 Data type: UInt16
Default:
0
Change:
At stop
Value Range:
0: General protocol
1: Special protocol
Description
This parameter defines the meaning of addresses 2000H and 2001H.
0: General protocol
The control word is written to 2000H, and DO output control is written to 2001H.
1: Special protocol
The special control word is written to 2000H, and the frequency reference is written to 2001H.
F8-60
Deceleration time for emergency stop
Address:
63548
Min.:
0.0
Unit:
s
Max.: 6500.0 Data type: UInt16
Default:
0.0
Change:
At once
Value Range:
0.0s to 6500.0s
Description
This parameter defines the deceleration time for emergency stop.
F8-61
LED operating panel jog
Address:
63549
Min.:
0
Unit:
-
Max.: 0 Data type: UInt16
Default:
0
Change: Unchangeable
Value Range:
-
Description
Switch to F8-61 using the operating panel of the power supply unit, press the ENT key to enter the jog
mode, and then press the UP/DOWN key to implement forward/reverse jog.