Generator 115V, 2-phase
Inductive consumers [kW] 4.0
Tab. 53 Maximum single-phase power supply loading
2.7.3.3 Operating limits
(According to EN 60034-22, table on page 10.)
Features Value
Design category G3
Voltage adjustment range [%] ±5
Static voltage deviation [%] 1
Maximum dynamic voltage drop [%] –15
Maximum dynamic voltage rise [%] 20
Maximum voltage settling time [ms] 1500
Maximum voltage asymmetry [%] 1
Tab. 54 Generator operating limits
2.7.3.4 Factor of output power reduction
The output power is dependent on installation altitude and ambient temperature.
Output power reduction
Ambient temperature [°F] 104 113
Altitude AMSL [ft] 3000 3000
Factor of output power reduction 1.0 0.95
Tab. 55 Output power reduction
2.7.4 Option ua
Air hose with hose reel
The machine is equipped with an additional discharge valve for this option.
Name Discharge valve Compressed air hose
Size ["] G 3/4 −
Number 1 −
Length [ft] − 66
Tab. 56 Additional discharge valve for the air hose