10 Parameter List
PumpDrive 2
175 of
212
Parameter Description Help text Possible settings Unit Factory setting
3-9-3-3 Dyn Press Comp n Data
Point
The setpoint compensation value is reached
at this point. Beyond that, the setpoint is
further increased with respect to the
specified value. Data is entered in %
referred to Maximum Motor Speed (3.2.2.2).
0,0 … 600,0 % 0,0
3-9-3-4 Setpoint Compensation Configurable setpoint compensation at data
point 3.9.3.2 or 3.9.3.3
Minimum to maximum limit of value range
set
Dependent on the
unit set
0,0
3-9-3-5 Minimum Setpoint
Compensation
Minimum setpoint compensation for
opening the swing check valve in the case
of low pump flow rates.
Minimum to maximum limit of value range
set
Dependent on the
unit set
0,0
3-9-4 Sleep Mode
3-9-4-1 Sleep Mode Sleep mode ON/OFF ▪ OFF
▪ ON
OFF
3-9-4-2 Setpoint Increase Pressure increase required for tank filling Minimum to maximum limit of value range
set
Dependent on the
unit set
3-9-4-3 Monitoring Period Configurable monitoring period until
setpoint increase or stop
0,0 … 600,0 s 20,0
3-9-4-4 Duration of Setpoint
Increase
Maximum duration of setpoint increase.
Stop is triggered if the setpoint is reached
within this window. The duration of the
setpoint increase must exceed the time of
the ramp defined for the increase.
0,0 … 600,0 s 20,0
3-9-4-5 Permissible Deviation Maximum permissible control deviation for
restart
Minimum to maximum limit of value range
set
Dependent on the
unit set
3-9-4-6 Minimum Runtime Minimum period of time between two stop
attempts in sleep mode
0,0 … 600,0 s 60,0
3-9-4-7 Ramp-up Time for
Setpoint Increase
Ramp-up time during which the setpoint is
increased
0,0 … 1000,0 s 30,0
3-9-4-8 Stop Speed The pump is stopped if the low flow limit or
stop speed of the pump is undershot due to
minimal withdrawal over period 3-9-4-3.
3-2-2-1 … 3-2-2-2 rpm 3-2-2-1
3-9-5 Energy Savings Meter
3-9-5-1 Energy Savings Meter Selection of method for energy savings
metering
Off FixedReferencePower
VariableReferencePower
OFF
3-9-5-2 Fixed Reference Power Configurable reference power of fixed
speed pump for energy savings meter
0,00…110,00 kW 0,00
3-9-5-3 CO2 Emissions per kWh Carbon dioxide emissions per kWh 0 …10000 g/kWh 500
3-9-5-4 Electricity Costs per kWh Electricity price per kWh 0,000…1000,000 0,140