EDS94ARNExxxx EN 2.3 - 06/2014 L 165
9400 regenerative power supply module | Parameter setting
"CAN on board" system bus
Implemented CANopen objects
I-1800
Communication parameter for the transmission of process data via TPDO1
[6-17] Assignment of the data telegram
Procedure for changing the identifier:
1. Deactivate the identifier (set bit 31 to "1").
2. Change the identifier.
3. Activate the identifier (set bit 31 to "0").
Index:
I-1800
Name:
TPDO1 communication parameter
Subindex Default setting Setting range (min. value | unit | max. value) Access Data type
0: Highest subindex supported 5 - (read access only) ro U8
1: COB-ID used by TPDO 0x180 + node ID 0 4294967295 rw U32
2: Transmission type 254 0 255 rw U8
3: Inhibit time 0 ms 0 0.1 ms 65535 rw U16
4: Reserved - - (reserved, read or write access results in the error
message 0x06090011)
rw U8
5: Event timer 0 ms 0 ms 65535 rw U16
Subindex Meaning Lenze code
1 Identifier TPDO1
The basic setting corresponds to the "Predefined
Connection Set": identifier = 0x180 + node ID
C00320/1
2 TPDO transmission type according to DS301 V4.02
Transmission type
( 113)
C00322/1
3 Minimum time interval between the transmission of
two identical TPDOs (see DS301 V4.02).
C00324/1
5 Cycle time for the transmission of PDOs with
transmission type "254".
C00356/1
8th byte 7th byte 6th byte 5th byte
Data 4 Data 3 Data 2 Data 1
Bit 31 Bit 30 Bit 29 ... bit 11 Bit 10 ... bit 0
0/1 0/1 Extended identifier* 11-bit identifier
* The extended identifier is not supported - bits 11 ... 29 must be set to "0".
Bit Setting
Bit 30 0 RTR to this PDO possible (Lenze).
1 RTR to this PDO not possible (cannot be set).
Bit 31 0 PDO is active.
1 PDO is not active.