Chapter 8 Table of Functions
G
8-10
No. Comm. No. Function Display Name Setting Range Initial Value
Shift in
Operation
Control Mode
V/F
SL
VC
SLT
VCT
76
Note15)
0h134C
CompFreq
Limit
Restriction of
compensational
frequency of
regeneration anc
avoidance for
pres
0 ~ 10.00 [Hz] 1.00 [Hz]
X O O O X X
77
0h134D
RegenAvd
Pgain
P-gain of
regeneration anc
avoidance for
press
0 ~ 100.0 [%] 50.0 [%]
O O O O X X
78
0h134E
RegenAvd
Igain
I-gain of
regeneration anc
avoidance for
pres
20 ~ 30000 [ms] 500 [ms]
O O O O X X
80 0h1350 Fire Mode Sel Fire Function Select
0 None
0:None X O O O X X1 Fire Mode
2 Fire Test
81
㨰
16) 0h1351 Fire Mode Freq Fire Mode Frequency 0~Max Freq[Hz] 60.00 X O O O X X
82 0h1352 Fireq Mode Dir
Fire Mode Operating
Direction
0 Forward
0:Forward X O O O X X
1 Reverse
83 - Fire Mode Cnt Fire Mode Counter 0~32767 0 X O O O X X
* The grey code refers to hidden code, emerging only in case of setting of the code.
Note 14)
ADV-71~72 is displayed only when ADV-70 (Run En Mode) is set as “DI Dependent”.
Note15)
ADV-76~78 is displayed only when ADV-75 (RegenAvd Sel) is set as “Yes”.
Note 16)
ADV-81~83 is displayed only when it is set as “Fire Mode” or “Fire Test” at ADV-80.