Chapter 8 Table of Functions
G
8-34
8.1.10 Parameter mode – Option card function group (
Î
APO)
No. Comm. No.
Function
Display
Name Setting Range
Initial
Value
Shift in
Operation
Control Mode
V/F
SL
VC
SLT
VCT
00 - Jum
p
Code
j
um
p
code
0 ~ 9
9
20
O
O
O
O
O
O
01
Note35)
0h1A01
Enc
Opt Mode
encoder function item
0
None
0:Non
e
O O O O O O
1
Feed-Bac
k
2
Reference
04
0h1A04
Enc
Type Sel
encoder type selection
0
Line Driver
0 :
Line
Driver
X O O O O O
1
Totem or Com
2
Open Collector
05
0h1A05
Enc
Pulse Sel
encoder pulse direction
0
(
A+B
)
0 :
(A+B)
X O O O O O
1
-
(
A+B
)
2
A
06
0h1A06
Enc
Pulse Num
Number of encoder pulses
10 ~ 4096
1024 X O O O O O
08
0h1A08
Enc Monitor Feed Back monitor
-
- O O O O O O
09
0h1A09
Pulse Monitor Reference monitor
-
- O O O O O O
10
0h1A0A
Enc Filter encoder input filter
0 ~ 10000 [ms]
3 O O O O O O
11
0h1A0B
Enc Pulse x1 Enc input minimum pulse
0 ~ 100 [kHz]
0.0 O O X O X O
12
0h1A0C
Enc Perc y1 output% at Enc minimum pulse
0 ~ 100 [%]
0.00 O O X O X O
13
0h1A0D
Enc Pulse x2 Enc input maximum pulse
0 ~ 200 [kHz]
100 O O X O X O
14
0h1A0E
Enc Perc y2 Enc maximum pulse
output%
0 ~ 100 [%]
100 O O X O X O
20
Note36)
0h1A14
Aux Motor Run
display of number of auxiliary motor
movemen
t
0 ~ 4
0 O O O O X X
21
0h1A15
Starting Aux starting auxiliary motor selection
1 ~ 4
1 X O O O X X
22
0h1A16
AutoOp Time auto change operation time
XX:XX [Min]
0:00 O O O O X X
23
0h1A17
Start Freq 1 1st auxiliary motor Start frequency
0 ~ 60[Hz]
49.99
O O O O X X
24
0h1A18
Start Freq 2 2nd auxiliary motor Start frequency O O O O X X
25
0h1A19
Start Freq 3 3nd auxiliary motor Start frequency O O O O X X
26
0h1A1A
Start Freq 4 4thauxiliary motor Start frequency O O O O X X
27
0h1A1B
Stop Freq 1 1st auxiliary motor stop frequency
15.00
O O O O X X
28
0h1A1C
Stop Freq 2 2nd auxiliary motor stop frequency O O O O X X
29
0h1A1D
Stop Freq 3 3nd auxiliary motor stop frequency O O O O X X
30
0h1A1E
Stop Freq 4 4th auxiliary motor stop frequency O O O O X X
31
0h1A1F
Aux Start D
T
auxiliar
y
motor startin
g
dela
y
time
0 ~ 3600.0 [s]
60.0
O
O
O
O
X X
3
2
0h1A20
Aux S
t
op D
T
auxiliar
y
motor stop dela
y
time
O
O
O
O
X X
33
0h1A21
Num of Aux auxiliar
y
motor number selection
0 ~ 4
4 X
O
O
O
X X
34
0h1A22
Regul Bypass bypass selection
0 N
o
0 : No X O O O X X
1 Ye
s
35
0h1A23
Auto Ch Mode auto change mode selection
0 None
1: Aux X O O O X X

Table of Contents

Other manuals for LSIS SV-iS7 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LSIS SV-iS7 series and is the answer not in the manual?

LSIS SV-iS7 series Specifications

General IconGeneral
BrandLSIS
ModelSV-iS7 series
CategoryInverter
LanguageEnglish

Related product manuals