Chapter 8 Table of Functions
G
8-37
No. Comm. No.
Function
Display
Name Setting Range
Initial
Value
Shift in
Operation
Control Mode
V/F
SL
VC
SLT
VCT
2
2
0h1B16
OL Trip Time
overload failure time
0 ~ 60 [s]
60.0
O
O
O
O
O
O
25
0h1B19
UL Warn Sel
light load alarm selection
0N
o
0 : No O O O O O O
1Ye
s
26
0h1B1
A
UL Warn Time
light load alarm time
0 ~ 600.0 [s]
10.0
O
O
O
O
O
O
27
0h1B1B
UL Trip Sel
light load failure selection
0 None
0:None O O O O O O
1 Free-Run
2Dec
28
0h1B1C
UL Trip Time
light load failure time
0 ~ 600 [s]
30.0 O O O O O O
29
0h1B1D
UL LF Level
light load lower limit level
10 ~ 30 [%]
30
O
O
O
O
O
O
30
0h1B1E
UL BF Level
light load upper limit level
30 ~ 100 [%]
30
O
O
O
O
O
O
31
0h1B1F
No Motor Trip
movement in case of no motor
detection
0 None
0: None O O O O O O
1 Free-Run
32
0h1B20
No Motor Level
no motor
detection current level
1 ~ 100 [%]
5 O OOOOO
33
0h1B21
No Motor Time
no motor
detection delay
0.1 ~ 10.0 [s]
3.0 O OOOOO
34
0h1B22
Thermal-T Sel
movement selection after motor
overheat detection sensor
detection
0 None
0 : None O O O O O O
1 Free-Run
2Dec
35
0h1B23
Thermal In
Src
motor overheat
detection sensor
input selection
0 None
0 : None X OOOOO
1V1
2I1
3V2
4I2
36
0h1B24
Thermal-T Lev
motor overheat detection
sensor failure level
0 ~ 100 [%]
50.0 O - - - - -
37
0h1B25
Thermal-T Area
motor overheat detection
sensor failure area
0Low
0 : Low O O O O O O
1High
40
0h1B28
ETH Trip Sel
electric thermal failure
selection
0 None
0 : None O O O O O O
1 Free-Run
2Dec
41
0h1B29
Motor Cooling
motor
cooling fan type
0Self-cool
0:Self-
cool
O O
OOOO
1 Forced-cool
4
2
0h1B2
A
ETH 1min
electric thermal 1 minute rating
120 ~ 200 [%]
150
O
O
O
O
O
O
43
0h1B2B
ETH Cont
electric thermal consecutive
rating
50 ~ 200 [%]
120 O OOOOO
50
0h1B32
Stall Prevent
stall preventing movement
Bit 0000 ~ 1111
0000 X O O X
OX
1 Accelerating
2
Steady speed
3 Decelerating
4 Flux Braking
51
0h1B33
Stall Freq 1
stall frequency 1
Start frequency 1
~ Stall frequency 1 [Hz]
60.00 O O O X
OX

Table of Contents

Other manuals for LSIS SV-iS7 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LSIS SV-iS7 series and is the answer not in the manual?

LSIS SV-iS7 series Specifications

General IconGeneral
BrandLSIS
ModelSV-iS7 series
CategoryInverter
LanguageEnglish

Related product manuals