Chapter 8 Table of Functions
G
8-43
8.1.15 User/Macro Mode –
MC1
No. Function Display Name Setting Range Initial Value
00
Jump Code
ump code
0 ~ 9
1
01
Acc Time
accelerating time
0 ~ 600 [s]
Below 75k
20
bove 90k
60
02
Dec Time
decelerating time
Below 75k
30
bove 90k
90
03
Cmd Source
operating command method
0 ~
1:Fx/R
-1
04
Freq
ef Src
frequency setting method
0 ~
2:V1
0
Control Mode
control mode
0 ~
0:V/
06
Aux Ref Src
auxiliary command setting method
0 ~ 4 2 : I1
07
Aux Calc Type
auxiliary command movement
selection
0 ~ 7 0
0
ux Ref Gain
auxiliary command gain
-200 ~ 200 [%] 100.0
09
V1 Polarity
V1 input polar selection
0 ~ 1 0 : Unipolar
10
V1 Filter
V1 input filter time constant
0 ~ 10000 [ms] 10
11
V1 Volt x1
V1input minimum voltage
0 ~ 10[V] 0.00
12
V1 Perc y1
output% at V1 minimum voltage
0 ~ 100 [%] 0.00
13
V1 Volt x2
V1input maximum voltage
0 ~ 10[V] 10.00
14
V1 Perc y2
Output % at V1 maximum voltage
0 ~ 100 [%] 100.00
15
V1 –Volt x1’
V1 –input minimum voltage
-10 ~ 0[V] 0.00
16
V1 –Perc y1’
output% at V1 –minimum voltage
-100 ~ 0 [%] 0.00
17
V1 –Volt x2’
V1–input maximum voltage
-10 ~ 0[V] -10.00
18
V1 –Perc y2
output% at V1 –maximum voltage
-100 ~ 0 [%] -100.00
1
V1 Inverting
rotation direction change
0 ~ 1 0 : N
20
I1 Monitor [mA]
I1 input amount displa
0 ~ 20 [mA] 0.00
21
I1 Polarity
I1 polarity displa
0 ~ 1 0
2
I1 Filte
I1 input filter time constant
0 ~ 10000 [ms] 10
23
I1 Curr x1
I1input minimum current
0 ~ 20 [mA] 4.00
24
I1 Perc y1
Output% at I1minimumcurrent
0 ~ 100 [%] 0.00
2
I1 Curr x2
I1input maximum current
4 ~ 20 [m
] 20.00
26
I1 Perc y2
output% at I1 maximum current
0 ~ 100 [%] 100.00
27
I1 Curr x1’
I1
Input minimal current
-20 ~ 0 [mA] 0.00
2
I1 Perc y1’
Output %at I1 - minimal current
-100 ~ 0 [%] 0.00
2
I1 Curr x2’
I1 - Input maximum current
-20 ~ 0 [m
] -20.00
30
I1 Perc y2’
Output% at I1 maximum current
-100 ~ 0 [%] -100.00
31
I1 Inverting
rotation direction change
0 ~ 1 0 : N
3
P1 Define
P1 terminal function setting
0 ~ 48
0:FX
33
P2 Define
P2 terminal function setting
1:RX
34 P3 Define
P3 terminal function setting
:BX