Chapter 4 Positioning Check
4- 2
(6) Operation Check through Jog Operation
• Check the operation of XGB positioning doing jog operation in the following sequence.
• This manual describes the axis X operation check when the pulse output mode is PLS/DIR mode
and the pulse output level is set as Low Active. Check the operation of axis Y. in the same manner.
(a) Check of Normal Direction Rotation of Jog
• Turn on the normal direction switch(P0010) of axis X, with the reverse direction switch of the
jog set at Off.
• Check whether the XGB positioning function normally generates jog normal direction output.
1) Check of the output LED
- P0020 (%QX0.0.0) : flashes quickly
- P0022 (%QX0.0.2) : stays ON
2) Check of area K
- Check whether the current position address is increasing by checking the current
position address area (axis X: K422 double word) with XG5000.
(b) Check of Normal Direction Stop of Jog
• Turn Off the jog normal direction switch (P0010, %IX0.0.16) during jog normal direction
operation, and check whether the output LED (P0020, %QX0.0.0, P0022, %QX0.0.2) is Off,
the current position address area (axis X: K422, %KD211 double word) with XG5000, and
whether the current position address has stopped increasing.
(c) Check of Reverse Direction Rotation of Jog
• Turn on the axis X jog reverse direction switch (P0012, %IX0.0.18)), with the normal direction
switch of the jog Off.
• Check whether the XGB positioning function is generating jog reverse direction output
normally.
1) Output LED Check
- P0020(%QX0.0.0) : flashes quickly
- P0022(%QX0.0.2) : stays OFF
2) Check of area K
- Check whether the current position address is decreasing by checking the current
position address area (axis X: K422, %KD211 double word) with XG5000
(d) Check of Reverse Direction Stop of Jog
• Turn Off the jog reverse direction switch (P0012, %IX0.0.18) during jog reverse direction
operation, and check whether the output LED (P0020, %QX0.0.0, P0022, %QX0.0.2) is Off,
the current position address area (axis X: K422, %KD211 double word) with XG5000, and
whether the current position address has stopped decreasing
(e) For compact standard type, there is not actual output P00040/P00044 and they are indicated by
LED.
(7) Finish of Positioning Check
• When you have finished checking whether the jog normal and reverse operation is normally
operating through the process above, end the check, make the positioning operation program to be
actually used and conduct the positioning operation.