NTP-008
: System Turnup 363-206-305
Page 2 of 8 Issue 3, June 2000
DDM-2000 F
IBER
R
EACH
W
IDEBAND
S
HELF
DO ITEMS BELOW IN ORDER LISTED. . . . .FOR DETAILS, GO TO
2. Verify that the DDM-2000 OC-3 host shelf is equipped with
Release 13 or 15 software. Verify that the DDM-2000 FiberReach
hosted shelf is equipped with Release 3 or 4 software. If not
equipped with proper software, upgrade the DDM-2000 OC-3 host
shelf and/or the FIberReach hosted shelf with the proper software.
3. Determine the optical loss of each optical span from office records
or by making the required measurements.
4.
NOTE:
The User Side/Network Side parameters of the
set-fecom: command must be set opposite at each end of
the optical spans (for example, see Figures 2 and 3).
Use the rtrv-fecom/set-fecom command to verify/set User
Side/Network Side parameters at each end of optical span being
established.
5.
NOTE:
The rtrv-sync: command retrieves the
Synchronization Report. This report displays the
provisioning and operational information on the
synchronization attributes of the DDM-2000. See the
"Commands and Reports" section of this manual for a
description of the rtrv-sync: command format.
Use the rtrv-sync: command to obtain the
Synchronization Report and verify if Sync
Autoreconfiguration is enabled. Use the set-sync: command to
enable the Sync Autoreconfiguration parameter, if required.
6. Verify no duplicate TID settings exist. The rtrv-ne: command
may be used at each shelf in the network to display settings. If
duplicates exist, determine new settings and use the set-ne
command to make new settings.