EasyManua.ls Logo

Lucent Technologies FiberReach DDM-2000 - Page 1260

Lucent Technologies FiberReach DDM-2000
1896 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NTP-024
: Circuit Order 363-206-305
Page 4 of 12 Issue 3, June 2000
DDM-2000 F
IBER
R
EACH
W
IDEBAND
S
HELF
DO ITEMS BELOW IN ORDER LISTED. . . . .FOR DETAILS, GO TO
NOTE:
In ring configurations, you should use the following rules in
establishing cross-connections in each ring:
1. All drop connections (including DRI, if present) from
the same STS-1 timeslot must be provisioned the
same, either all VT1.5 or STS-1.
2. If all 28 VT1.5s (DS1s) in an STS-1 are being passed
through at a node in a VT1.5 path-switched ring, then
the cross- connection may be provisioned as either a
pass-through STS-1 or VT1.5. However, if you
anticipate dropping VT1.5s from the pass-through
node in the future, you should provision the
pass-throughs as VT1.5 cross-connections.
3. On STS-1 path-switched rings, all nodes in the ring
must be provisioned as STS-1 cross-connections.
NOTE:
Up to 84 DS1s may be terminated in a ring network. Once a
DS1 is terminated, that timeslot must be reserved in both
directions around the ring to the far end. Therefore, if a DS1
is terminated (cross-connected) to a function group on a
near-end and far-end terminating shelf, it must also be
pass-through cross-connected in every shelf in the network.
See "Cross-Connection Provisioning" in the "Administration
and Provisioning" section of this manual for more information
on cross connections.
Use the ent-crs-vt1: or ent-crs-sts1: command at the
new shelf to make all required
pass-through
cross-connections
(for example, ent-crs-vt1:m-1-1-1,m-1-1-1 or
ent-crs-sts1:m-1,m-1). Pass-through cross-connections
must be made at the new shelf to correspond to each terminating
cross- connection present on every shelf in the ring network. (See
Figure 1.)

Table of Contents

Related product manuals