TAP-112
: Trouble Clearing 363-206-305
Page 16 of 16 Issue 3, June 2000
DDM-2000 F
IBER
R
EACH
W
IDEBAND
S
HELF
44. At far-end terminal, reset
SYSCTL
by unseating and reseating
SYSCTL
or by
using a CIT and the reset command, if not already performed. If
FAULT
LED
is still flashing after a reset, refer to
DLP-501
and replace
SYSCTL
at far-end
terminal.
45.
STOP. YOU HAVE COMPLETED THIS PROCEDURE
.
46. Replace
OLIU
s at far end that are associated with the Source Address of
the inc. OC3 line AIS or inc. OC12 line AIS alarm message.
Reference:
DLP-523
47.
STOP. YOU HAVE COMPLETED THIS PROCEDURE.
48. Check far-end
TGS/TG3
option switches for proper line coding and frame
format settings (
rtrv-sync:
). If no trouble found, check incoming timing
reference signals. If timing reference signals are bad, issue trouble report of
bad incoming timing reference signal(s). If no trouble found with timing
references, replace far-end
TGS/TG3
circuit packs.
Reference:
DLP-523
49.
STOP. YOU HAVE COMPLETED THIS PROCEDURE
.