DLP-514
: Detailed Level Procedure 363-206-305
Page 4 of 22 Issue 3, June 2000
DDM-2000 F
IBER
R
EACH
W
IDEBAND
S
HELF
NOTE:
A dual-homed OC-1 ring configuration requires that the first FiberReach
MAIN-1 OLIU
connect to
FN ( )-1 OLIU
on one host OC-3 shelf. The last
FiberReach
MAIN-2 OLIU
connects to the
FN ( )-2(P) OLIU
on the other
host OC-3 shelf. Intermediate FiberReach shelves on the same OC-1
ring connect from
MAIN-2 OLIU
at one FiberReach shelf to the
MAIN-1
OLIU
at an adjacent FiberReach shelf (node).
NOTE:
For DDM-2000 OC-3 or OC-12 ring configurations, optical fibers extend
in two different directions to make up the ring. At each shelf (node) in the
ring, the OC-3/OC-12 shelf
MAIN 1[MAIN-B-1] OLIU
will connect to the
FiberReach
MAIN-2
OLIU
in another node , and the OC-3/OC-12
MAIN
2(P)[MAIN-B-2(P)] OLIU
will connect to the FiberReach
MAIN-1 OLIU
in
a separate node.
NOTE:
This single-homed OC-3 ring or linear extension to OC-12 node
configuration requires that the
FN ( )-1 OLIU
on the OC-12 shelf connect
to the
MAIN-1 OLIU
at the FiberReach shelf from the OC-12 shelf. The
MAIN-2 OLIU
at the FiberReach shelf on the OC-3 ring or linear
extension connects to
FN ( )-2(P) OLIU
on the host OC-12 shelf.
NOTE:
A dual-homed OC-3 ring to OC-12 node configuration requires that the
first FiberReach
MAIN-1 OLIU
connect to
FN ( )-1 OLIU
on one host
OC-12 shelf. Intermediate FiberReach shelves on the same OC-3 ring
connect from
MAIN-2 OLIU
at one FiberReach shelf to the
MAIN-1 OLIU
at an adjacent FiberReach shelf (node). The last FiberReach
MAIN-2
OLIU
connects to the
FN ( )-2(P) OLIU
on the other host OC-12 shelf.
NOTE:
This single-homed OC-3/OC-12 ring or linear extension to FT-2000 node
configuration requires that the
LS INTFC
slots
1A
thru
8A
on the host
FT-2000 shelf connect to the
MAIN-1 OLIU
at the FiberReach shelf from
the FT-2000 shelf. The
MAIN-2 OLIU
at the FiberReach shelf on the
OC-3/OC-12 ring or linear extension connects to companion
LS INTFC
slots
1B
thru
8B
on the host FT-2000 shelf.
NOTE:
A dual-homed OC-3/OC-12 ring to FT-2000 node configuration requires
that the first FiberReach
MAIN-1 OLIU
connect to any
LS INTFC
slots
1A
thru
8B
on one host FT-2000 shelf. Intermediate FiberReach shelves
on the same OC-3/OC-12 ring connect from
MAIN-2 OLIU
at one
FiberReach shelf to the
MAIN-1 OLIU
at an adjacent FiberReach shelf
(node). The last FiberReach
MAIN-2 OLIU
connects to any
LS INTFC
slots
1B
thru
8B
on the other host FT-2000 shelf.