363-206-305 Detailed Level Procedure:
DLP-529
Issue 3, June 2000 Page 5 of 6
DDM-2000 F
IBER
R
EACH
W
IDEBAND
S
HELF
25. Does test set STOP indicator light and TIME display stop counting time?
If YES, proceed to Step 27.
If NO, continue with Step 26.
26.
!
DANGER:
A high discharge current is present at connector head if
TESTING
indicator is lit. Batteries must not be connected or disconnected when
TESTING
indicator is lit.
There is a defective test set. Allow test to run for 15 minutes as shown on TIME
display. When COMPLETE indicator lights, unplug battery, and return test set
for repair.
27.
!
DANGER:
A high discharge current is present at connector head if
TESTING
indicator is lit. Batteries must not be connected or disconnected when
TESTING
indicator is lit.
Depress test set START/CONTINUE button.
28. Does test set TESTING indicator light, STOP indicator go off, and TIME
display start counting time?
If YES, continue with Step 29.
If NO, proceed to Step 35.
29. Allow test set to run for 15 minutes as shown on TIME display.
30. During 15-minute test period, does test set show REPLACE?
If YES, continue with Step 31.
If NO, proceed to Step 32.
31. Note that battery being used is defective.
32. After 15 minutes, does COMPLETE indicator light?
If YES, continue with Step 33.
If NO, proceed to Step 35.
33. Unplug battery. Store connector head in test set cover. Reinstall cover.
34. STOP. YOU HAVE COMPLETED THIS PROCEDURE.