DLP-529
: Detailed Level Procedure 363-206-305
Page 4 of 6 Issue 3, June 2000
DDM-2000 F
IBER
R
EACH
W
IDEBAND
S
HELF
19. Have
TIME
display and
STATUS
indicators been tested for each good
BATT
plug position?
If
YES
, proceed to
Step 21.
If
NO
, continue with
Step 20.
20.
!
DANGER:
A high discharge current is present at connector head if
TESTING
indicator is lit. Batteries must not be connected or disconnected when
TESTING
indicator is lit.
Ensure that
TESTING
indicator is not lighted. (
READY
indicator lit). Unplug
battery pack and repeat from Step 5.
21.
!
DANGER:
A high discharge current is present at connector head if
TESTING
indicator is lit. Batteries must not be connected or disconnected when
TESTING
indicator is lit.
Depress test set
START/CONTINUE
button.
22. Does test set
TESTING
indicator light,
READY
indicator go off, and
TIME
display start counting time?
If
YES
, proceed to
Step 24.
If
NO
, continue with
Step 23.
23.
!
DANGER:
A high discharge current is present at connector head if
TESTING
indicator is lit. Batteries must not be connected or disconnected when
TESTING
indicator is lit.
There is a defective test set. Depress
STOP
button, unplug battery, and return
test set for repair.
24. Depress test set
STOP
button.