EasyManua.ls Logo

Lucent Technologies FiberReach DDM-2000 - Page 395

Lucent Technologies FiberReach DDM-2000
1896 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
363-206-305
Administration and Provisioning
Issue 3 June 2000
8-37
In Figure 8-1, the example configuration is a ring network with two ring fibers and
six nodes. Ring 1 carries ring traffic in the clockwise direction while Ring 2 carries
ring traffic in the counterclockwise direction. In the example configuration, Node 1
is a DDM-2000 OC-3 shelf equipped with 27-type OLIU circuit packs in the Main
slots, MXRVOs in Function Unit A, and DS1 or DS1PM circuit packs in the Low-
Speed Group A slots. Nodes 2 through 6 are DDM-2000 FiberReach Multiplexer
shelves with 26-type OLIU circuit packs in the Main slots and DS1 or DS1PM
circuit packs in the Low-Speed Group A slots. All shelves are properly installed
and provisioned. This example is for DS1 services. See "System Turnup/Circuit
Order" in the TOP section of this manual for actual procedures.
Ring configurations support manual VT1.5 cross-connections. Manual cross-
connections must be made at
each
node in the network for each circuit being
established. Drop cross-connections are made at the drop nodes where service
enters or exits the node (Nodes 1 and 5) and pass through cross-connections are
made at
each
intermediate node (Nodes 2, 3, and 5).
It is recommended that pass-through cross-connections be entered first, as
shown below, to avoid transient alarms during provisioning.
The following commands may be used to delete, enter, and retrieve cross-
connections:
dlt-crs-vt1
,
ent-crs-vt1
and
rtrv-crs-vt1
. See Chapter
11, "Commands and Reports," for a description of these commands.
To establish the end-to-end DS1 circuit from Node 1 to Node 5, as shown in
Figure 8-1, enter a cross-connection at each node as follows:
1. Enter the following pass-through cross-connections at Nodes 2, 3, and 5:
ent-crs-vt1:m-1-2-3,m-1-2-3:cct=twoway;
2. Enter the following cross-connection to drop the VT1.5 channel from the
OC-1 ring to a DS1 interface at Node 1:
ent-crs-vt1:m-1-2-3,a-2-3:cct=twoway;
3. Enter the following cross-connection to drop the VT1.5 channel from the
OC-1 ring to a DS1 interface at Node 4, a DDM-2000 FiberReach
Wideband shelf:
ent-crs-vt1:m-1-2-3,a-1-3:cct=twoway;
4. Test both paths around the ring. Since DDM-2000 uses non-revertive path
switching to minimize the number of hits on services, the initial path
selection is arbitrary. Use
rtrv-state-path
and
sw-path-vt1
commands to test both ring paths around the ring network at the drop
nodes of the new service. The
sw-path-vt1
command should be limited
to the addresses that are being tested. For the example, the commands to
be used at Node 1 and Node 4 are:
sw-path-vt1:m1-1-2-3
and
sw-path-vt1:m2-1-2-3
.

Table of Contents

Related product manuals