For flush-mount method 1 (without angle brackets and frame), the procedure is
as follows:
Before the P634 can be installed into a control panel, the local control panel (or
the front element of the case for devices with detachable display) must be taken
down. The local control panel is removed as described below:
1.
Remove both top and bottom hinged flaps from the device. (Lift/lower
both hinged flaps 180° up/down. Hold them in the middle and bend them
slightly. The side mountings of both hinged flaps can then be disengaged.)
2.
Remove the M3.5 screws (see Fig. 5-3, (p. 5-8)).
3.
Then remove the local control panel.
WARNING
The local control panel (or front element) is connected to processor module P
by a plug-in connecting cable. Make sure the connector position is correct. Do
not bend the connecting cable!
Then remove the lower M4 screws and only loosen the upper M4 screws (see
Fig. 5-3, (p. 5-8)). Now insert the P634 into the panel opening from the rear so
that the upper M4 screws fit into the corresponding holes. Then tighten all the
M4 screws. After this, replace the local control panel.
WARNING
When replacing the local control panel, take care not to tighten the M3.5
screws with too much strength! (Fastening torque 1.5 to 1.8 Newton meters.)
If the control panel thickness is 2 mm, the longer M3.5 and M4 bolts must be
used. Longer screws are enclosed within the device packing.
5 Installation and Connection P634
P634/EN M/R-42-A // P634311653 5-7