Parameter Address
Default Min Max Unit Logic Diagram
[spacer]
COMM1: Reg.asg. selec. sig.
003 211
060 000: MAIN: Without function Fig. 3-10, (p. 3-15)
[spacer]
MODBUS registers in the range 10301 to 10400 are assigned to the selected
signals. Assignment is made in the order of selection. This means that the first
signal is given the register no. 10301, the second the register no. 10302, etc.
Note: This setting is hidden unless the MODBUS protocol is enabled.
[spacer]
COMM1: Reg.asg. sel. m.val.
003 212
060 000: MAIN: Without function Fig. 3-10, (p. 3-15)
[spacer]
MODBUS registers in the range 30301 to 30400 are assigned to the selected
measured values. Assignment is made in the order of selection. This means that
the first measured value is given the register no. 30301, the second the register
no. 30302, etc.
Note: This setting is hidden unless the MODBUS protocol is enabled.
[spacer]
COMM1: Reg.asg. sel. param.
003 213
060 000: MAIN: Without function Fig. 3-10, (p. 3-15)
[spacer]
MODBUS registers in the range 40301 to 40400 are assigned to the selected
parameters. Assignment is made in the order of selection. This means that the
first parameter is given the register no. 40301, the second the register no.
40302, etc.
Note: This setting is hidden unless the MODBUS protocol is enabled.
[spacer]
COMM1: Delta t (MODBUS)
003 152
5 1 120 s Fig. 3-10, (p. 3-15)
[spacer]
All MODBUS registers are transmitted again through the communication
interface after this time has elapsed.
Note: This setting is hidden unless the MODBUS protocol is enabled.
[spacer]
COMM1: Autom.event confirm.
003 249
0: Without Fig. 3-10, (p. 3-15)
[spacer]
Setting specifying whether an event must be confirmed by the master in order
for an event to be deleted from the 'event queue'.
Note: This setting is hidden unless the MODBUS protocol is enabled.
[spacer]
COMM1: Phys. Charact. Delay
003 241
0 0 254 Bit Fig. 3-11, (p. 3-16)
[spacer]
Number of bits that must pass between the receipt of the 'request' and the start
of sending the 'response'.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
[spacer]
COMM1: Phys. Char. Timeout
003 242
40 0 254 Bit Fig. 3-11, (p. 3-16)
[spacer]
Number of bits that may be missing from the telegram before receipt is
terminated.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.