Parameter Address
Default Min Max Unit Logic Diagram
Inverse-time overcur
rent protection
IDMT1: General enable USER
031 141
0: No Fig. 3-116, (p. 3-162)
[spacer]
IDMT2: General enable USER
031 142
0: No
[spacer]
IDMT3: General enable USER
031 143
0: No
[spacer]
Disabling and enabling the inverse-time overcurrent protection function.
[spacer]
IDMT1: Select. meas. input
019 106
0: End a Fig. 3-115, (p. 3-161)
[spacer]
IDMT2: Select. meas. input
019 116
1: End b
[spacer]
IDMT3: Select. meas. input
019 126
2: End c
[spacer]
Selection of the measuring input that provides the measured variables
monitored by the inverse-time overcurrent protection function.
P634 7 Settings
7-90 P634/EN M/R-42-A // P634311653