Parameter Address
Default Min Max Unit Logic Diagram
[spacer]
DTOC2: I> dynamic PSx
076 161 077 161 078 161 079 161
1.00 0.10 30.00 Inom
[spacer]
DTOC3: I> dynamic PSx
076 181 077 181 078 181 079 181
1.00 0.10 30.00 Inom
[spacer]
DTOC4: I> dynamic PSx
099 140 099 141 099 142 099 143
1.00 0.10 30.00 Inom
[spacer]
Setting for operate value I> in dynamic mode. This operate value is only
effective while the hold time for dynamic parameters is elapsing.
[spacer]
DTOC1: I>> dynamic PSx
076 152 077 152 078 152 079 152
1.00 0.10 30.00 Inom Fig. 3-108, (p. 3-154)
[spacer]
DTOC2: I>> dynamic PSx
076 162 077 162 078 162 079 162
1.00 0.10 30.00 Inom
[spacer]
DTOC3: I>> dynamic PSx
076 182 077 182 078 182 079 182
1.00 0.10 30.00 Inom
[spacer]
DTOC4: I>> dynamic PSx
099 144 099 145 099 146 099 147
1.00 0.10 30.00 Inom
[spacer]
Setting for operate value I>> in dynamic mode. This operate value is only
effective while the hold time for dynamic parameters is elapsing.
[spacer]
DTOC1: I>>> dynamic PSx
076 153 077 153 078 153 079 153
1.00 0.10 30.00 Inom Fig. 3-108, (p. 3-154)
[spacer]
DTOC2: I>>> dynamic PSx
076 173 077 173 078 173 079 173
1.00 0.10 30.00 Inom
[spacer]
DTOC3: I>>> dynamic PSx
076 109 077 109 078 109 079 109
1.00 0.10 30.00 Inom
[spacer]
DTOC4: I>>> dynamic PSx
099 148 099 149 099 150 099 151
1.00 0.10 30.00 Inom
[spacer]
Setting for operate value I>>> in dynamic mode. This operate value is only
effective while the hold time for dynamic parameters is elapsing.
[spacer]
DTOC1: tI> PSx
076 057 077 057 078 057 079 057
1.00 0.00 100.00 s Fig. 3-109, (p. 3-155)
[spacer]
DTOC2: tI> PSx
076 077 077 077 078 077 079 077
1.00 0.00 100.00 s
[spacer]
DTOC3: tI> PSx
076 187 077 187 078 187 079 187
1.00 0.00 100.00 s
[spacer]
DTOC4: tI> PSx
099 088 099 089 099 090 099 091
1.00 0.00 100.00 s
[spacer]
Setting for operate delay I>.
P634 7 Settings
7-160 P634/EN M/R-42-A // P634‑311‑653