Parameter Address
Default Min Max Unit Logic Diagram
[spacer]
MAIN: Current IB,d prim.
006 024
Not measured 0 65000 A
[spacer]
Display of phase current B of end a, b, c or d, respectively, as a primary
quantity.
[spacer]
MAIN: Current IC,d prim.
007 024
Not measured 0 65000 A
[spacer]
Display of phase current C of end a, b, c or d, respectively, as a primary
quantity.
[spacer]
MAIN: Current Ineg a prim.
005 125
Not measured 0 65000 A
[spacer]
MAIN: Current Ineg b prim.
005 129
Not measured 0 65000 A
[spacer]
MAIN: Current Ineg c prim.
005 136
Not measured 0 65000 A
[spacer]
MAIN: Current Ineg d prim.
005 140
Not measured 0 65000 A
[spacer]
Display of the negative-sequence current of the respective end as a primary
quantity.
[spacer]
MAIN: Current Ipos a prim.
005 127
Not measured 0 65000 A
[spacer]
MAIN: Current Ipos b prim.
005 134
Not measured 0 65000 A
[spacer]
MAIN: Current Ipos c prim.
005 138
Not measured 0 65000 A
[spacer]
MAIN: Current Ipos d prim.
005 146
Not measured 0 65000 A
[spacer]
Display of the positive-sequence current of the respective end as a primary
quantity.
[spacer]
MAIN: Current IN,a prim.
005 121
Not measured 0 65000 A
[spacer]
MAIN: Current IN,b prim.
005 122
Not measured 0 65000 A
[spacer]
MAIN: Current IN,c prim.
005 123
Not measured 0 65000 A
[spacer]
Display of the residual current calculated by the P634 from the sum of the phase
currents (of the respective end) as a primary quantity.
[spacer]
MAIN: Current IY,a prim.
005 131
Not measured 0 65000 A
8 Information and Control Functions P634
P634/EN M/R-42-A // P634‑311‑653 8-7