EasyManua.ls Logo

Micom P634 - Page 549

Micom P634
840 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Address
Default Min Max Unit Logic Diagram
[spacer]
MAIN: Current IY,c p.u.
005 153
Not measured 0.000 25.000 Inom
[spacer]
Display of the current value as a quantity referred to I
nom
measured by the P634
at the T14, T24 or T34 transformers.
[spacer]
MAIN: IP,max,add p.u.
005 114
Not measured 0.000 25.000 Inom Fig. 3-49, (p. 3-80)
[spacer]
Display of the maximum phase current for the virtual end, referred to I
nom
. The
virtual end is formed according to the selection at MAIN: Current
summation.
[spacer]
MAIN: IP,min,add p.u.
005 110
Not measured 0.000 25.000 Inom Fig. 3-49, (p. 3-80)
[spacer]
Display of the minimum phase current for the virtual end, referred to I
nom
. The
virtual end is formed according to the selection at MAIN: Current
summation.
[spacer]
MAIN: Current IA,add p.u.
005 038
Not measured 0.000 25.000 Inom Fig. 3-49, (p. 3-80)
[spacer]
MAIN: Current IB,add p.u.
006 038
Not measured 0.000 25.000 Inom Fig. 3-49, (p. 3-80)
[spacer]
MAIN: Current IC,add p.u.
007 038
Not measured 0.000 25.000 Inom Fig. 3-49, (p. 3-80)
[spacer]
Display of phase current A, B or C, respectively, for the virtual end, referred to
I
nom
. The virtual end is formed according to the selection at MAIN: Current
summation.
[spacer]
MAIN: Curr. Ineg,add p.u.
005 149
Not measured 0.000 25.000 Inom
[spacer]
Display of negative-sequence current for the virtual end, referred to I
nom
. The
virtual end is formed according to the selection at MAIN: Current
summation.
[spacer]
MAIN: Curr. Ipos,add p.u.
005 150
Not measured 0.000 25.000 Inom
[spacer]
Display of positive-sequence current for the virtual end, referred to I
nom
.
The virtual end is formed according to the selection at MAIN: Current
summation.
[spacer]
MAIN: Current IN,add p.u.
005 155
Not measured 0.000 25.000 Inom Fig. 3-49, (p. 3-80)
[spacer]
Display of residual current for the virtual end, referred to I
nom
. The virtual end is
formed according to the selection at MAIN: Current summation.
8 Information and Control Functions P634
P634/EN M/R-42-A // P634311653 8-11

Table of Contents