Parameter Address
Default Min Max Unit Logic Diagram
IEC 61850
Communication
IEC: Sel.spontan.sig.test
104 245
060 000: MAIN: Without function
[spacer]
IEC: Test spont.sig.start
104 246
0: don't execute
[spacer]
IEC: Test spont.sig. end
104 247
0: don't execute
[spacer]
IEC: Sel. pos. DEV test
104 248
0: Not assigned
[spacer]
IEC: Test position DEV
104 249
0: don't execute
Parameter Address
Default Min Max Unit Logic Diagram
Measured data input
MEASI: Reset Tmax USER
003 045
0: don't execute
[spacer]
Resetting measured maximum temperatures Tmax and Tmax Tx (x=1...9) to
updated measured values.
Parameter Address
Default Min Max Unit Logic Diagram
Binary and analog
output
OUTP: Reset latch. USER
021 009
0: don't execute Fig. 3-29, (p. 3-46)
[spacer]
Reset of latched output relays from the user interface.
[spacer]
OUTP: Relay assign. f.test
003 042
060 000: MAIN: Without function Fig. 3-30, (p. 3-47)
[spacer]
Selection of the relay to be tested.
[spacer]
OUTP: Relay test
003 043
0: don't execute Fig. 3-30, (p. 3-47)
[spacer]
The relay selected for testing is triggered for the duration set at OUTP: Hold-
time for test.
[spacer]
OUTP: Hold-time for test
003 044
1 1 10 s Fig. 3-30, (p. 3-47)
[spacer]
Setting for the time period for which the selected output relay is triggered for
functional testing.