Version Changes
CBF_x The release condition for the function has been
dissociated from the drop-out of the internal trip signal.
Therefore the sequence will now only be stopped when
a loss of load/undercurrent condition has occurred or
when the CB signals that its contacts are open.
Bug fixing:
●
The time tags for the CBF_1: Ready (038 009),
CBF_2: Ready (043 076), CBF_3: Ready (043
106) and CBF_4: Ready (043 136) spontaneous
signals (according to the communications
protocol per IEC-60870-5-10x) and the entry in
the operating data memory did not match.
IEC Bug fixing pertaining to the COMTRADE fault files which
a client receives via the IEC 61850 interface:
Stating of “Control Modes” in the ICD file has been
corrected. The IEC data model is not affected by this.
Bug fixing:
●
The automatically generated data file names are
now correct with fault numbers exceeding 999.
Data file names are issued according to this
format:
yyyymmdd_HHMMSS_xxx_rNNNN.eee
With: yyyy = year
mm = month
dd = day
HH = hour
MM = minute
SS = second
xxx = millisecond
r = permanent single character
NNNN = fault number
eee = file extension
In previous versions the dot (.) was overwritten
for fault numbers exceeding 999.
●
The correct number of binary channels is now
entered in the COMTRADE configuration file
(*.cfg). In the previous version the number of
binary channels was given as n*16+1 when,
because of the function configuration, n*16 binary
information signals were recorded. Therefore
values stored in the *.cfg file and the *.dat file did
not match.
P634
‑308
‑407/408
‑621
Hardware
No changes.
P634 A5 P634 Version History
A5-20 P634/EN M/R-42-A // P634‑311‑653