Version Changes
Release: 2009-01-08
Diagram
No changes.
Software
IEC The data object LN_CFG has been extended in logical
nodes Dt1NgsPTOC1, Dt2NgsPTOC1 and Dt3NgsPTOC1.
Further logical nodes have been added:
●
PloGGIO4
●
IdcGGIO1
●
RtdGGIO1
The AlmGGIO logical node has been extended by the
following signals:
●
Alm5: THRM1: CTA error (039 127)
●
Alm6: THRM2: CTA error (039 187)
●
Alm7: MEASI: PT100 faulty (040 190)
●
Alm8: MEASI: Overload 20mA input (040
191)
●
Alm9: MEASI: Open circ. 20mA inp. (040
192)
●
Alm10: CTS: Operated (updating) (036 099)
The ‘Bl.f.’ data objects are now available in all nodes:
PTOC, PTOV, PTUV, PTTR, PTOF, PTUF, RBRF, PVPH.
Because of this, the ‘Blocking EXT’ condition has been
removed from the ‘MODE’.
The parameter at address (104 232) IEC: Dead band
VPP has been renamed to IEC: Dead band V.
Since the corresponding measured values are not
provided by the P634, the following addresses have
been deleted:
●
IEC: Dead band VPG (104 233)
●
IEC: Dead band P (104 235)
●
IEC: Dead band Z (104 237)
●
IEC: Dead band ASC (104 239)
●
IEC: Update cycle energy (104 060)
Bug fixing:
●
The standardized model according to WYE class
(e.g. ‘phsA’ instead of ‘adphsA’) is now applied
with the data model for measured values for
resultant current forming (‘virtual end’).
COMM1 Bug fixing with the use of the MODBUS communication
protocol:
Faults can now be read out.
A5 P634 Version History P634
P634/EN M/R-42-A // P634‑311‑653 A5-21